|
|
|
|
This web site
is intended for professionals who have mechanical & electrical
skills who are aware that errors can occur in technical writing
and are willing to verify the accuracy of the information using
other sources such as the NEC handbook. Links
to books click
here
|
- Kitchens
require two dedicated 20 amp small appliance circuits.
nec 210-52(b2-3)Only outlet receptacles in the dining rooms and
kitchens can be connected to these two circuits.
No lights, no built-in appliances of any kind can tap into the two dedicated
20 amp small appliance circuits
- Evenly
distribute the electrical loads between the two dedicated circuits nec
210-11(b).. You can alternate each successive receptacle on the
wall between circuit #1 and #2 or divide the circuit into one half the
kitchen for each circuit. planning kitchen loads.
- You
can ire the two dedicated circuit using (2) 12-2 romex wires or (1)
12-3 romex wire. If you choose to use 12-3 you must have a common tie
circuit breaker that turns off both circuits if one of them trips.
- Counter
tops wider than one foot must have an outlet
210-52(c)(1)
- Receptacle
outlets must be placed on counter tops every four feet
A coffee pot with a 2' cord must reach a receptacle no matter where it is placed on a counter top. When two countertops meet at ninety degrees the coffepot might reach everywheren but there might be four and one-half feet linerly beteen outlets. Here, use the four foot rule strictly as measured across each wall. A 5 foot counter must have (2) outlets and a 6 foot counter must have at least (3) outlet receptacles. 210-52(a). more info
-
nec 210-52(b)3(c)5.Receptacles
cannot be placed face-up on the counter.nec
-
Countertop
receptacles cannot be mounted on the wall higher than 18" from
the surface of the countertop. nec 210-52(b)3(c)5.
- Ground
fault interrupters must be installed on all counter receptacles
in a kitchen. Outlets for stoves and refrigerators are generally not
placed on GFCI's.
- In
some cases countertop outlets including peninsular and island countertops
can be placed in the bottom of cabinets no more than 18" high
(1996 nec) or (20" high 2001nec). nec 210-52-c-5
(confirm this with your inspector) . In other cases outlets can be
mounted up to 6" below
the countertop with an extension in the code allowing 12" below
the countertop.
exceptions nec 210-52)(c)(5)
-
Counter tops on kitchen islands must have at least one outlet where
counter top
has an overhang less than 6" 210-52 (c)(5)
more info
.
- Island
and peninsular countertops must have an outlet receptacle
-
Island countertop outlets cannot be lower than 6" from island top
or 12" If there is a cabinet above the countertop in which a receptacle
ca be placed you cannot mount a receptacle on the face of the lower
cabinet lower than 6" handicap exceptions
and others 210-52)(c)(5)
- Countertop
that has receptacles mounted below the surface cannot protrude more
than 6" over the cabinet base. nec 210-52
c-5
-
Kitchens with disposals, dishwashers, compactors, sink insta-heaters,
and ice makers may be required by the local inspector to each have
dedicated
20 amp circuit. Otherwise the code allows
any general purpose circuits to be used if the the power consumed by
the
individual
appliance
does not draw more than 50% of the circuits load. A 900 watt disposal
draws less than the 2400 watts available on a 20 amp circuit while
most
dishwashers draw more than 50% of the 2400 watts and therefore needs
a dedicated circuit. If you do not know the loads wire dedicated 20
amp circuits to each appliance nec 210-23(a) Check
with your inspector. The rule of thumb is to use dedicated circuits
-
Counter microwave can plug into countertop receptacles. If the microwave Anchor
is built-in you must add another 20 amp dedicated circuit.nec
-
The refrigerator can have a dedicated 15 or 20 amp circuit nec of the
single outlet receptacle on that circuit is rated to that circuit nec
This means that if it is a 20 amp circuit then a special 20 amp receptacle
will be needed. Circuits with two or more receptacles do not fall under
this rule.nec
- The
receptacle loads must be evenly distributed in the room and on the countertops.
Some local inspectors require the electrician to alternate each successive
receptacle between the two 20 amp small appliance circuits.
nec
- GFCI not required for refrigerator, compactor, disposal,
or dishwasher. 210-8(a)6
- Light
switches must be placed at every entry to a kitchen.
-
Lights cannot be connected to any of the kitchen outlet circuits
nec
-
Three and four-way switches must be used at multiple entry and exits
to the kitchen
-
The nearest switch at every entry (in a bank of switches) must operate
the
main lights.
- Outlet
receptacles must be installed within six feet of each side
of any door leading outside. More info
& drawings
-
Unobstructed wall space not associated with counter tops greater
than two feet in width must have an outlet. Measure wall distance around
corners.
nec 210-52-a-2
More info & drawings
- Unobstructed
kitchen wall space must have an outlet every six feet. Start measuring
at door entry or exit on both sides for 6' measurement 210-52
(a)1. These outlets cannot be any higher
off the floor than 5'6"
210-52 (a)1-2.
- Stove
ventilation fan circuit must be separate from the kitchen
receptacle circuits
- You
cannot install a circuit breaker box in a cupboard, or behind
and over a kitchen appliance. More
info
- A
wall mounted electric clock can be connected to the small appliance
circuits 210-52(b)(2)exception
1
- Built-in appliances
and areas inaccessible to small appliances are not to be part of the
small appliance circuits. Read carefully the details in the NEC code.
210-52(c)5
under receptacle outlet location.
- You cannot install
an outlet receptacle face up on a countertop
nec 210-8-a-7.
- You
can use more than two dedicated circuits in a kitchen for outlets.
20 amp for microwave, 15 or 20 amp circuit for refrigerator.nec
210-52-3(b)1.
- A
countertop gas stove, or freestanding gas stove can be plugged into
the dedicated circuits. 210-52(b)(2)
exception 2
- Separate
kitchens, even adjoining must have two dedicated small appliance circuits
nec 210-52-b-3.
- Baseboard
heaters with receptacles mounted in them can count as wall space receptacles
but the heater must be connected to a dedicated circuit and the receptacle
must be connected to one of the small appliance circuits. Electric wall
heaters with an included receptacle are allowed by the nec, however,
if not there must be a receptacle on either side, not below the heater.
nec 90-7, 110-3(b), 424-9, 210-50(b). If
you install a baseboard heater the wire you use must carry 125% of the
nameplate current rating of the eater i.e. if the baseboard is 18 amps
multiply 18 X 125% to get 25.5 amps thus you would need # 10 wire to
connect the heater on a dedicated circuit to the sub panel.
-
The kitchen is considered a habitable room when reading and interpreting
the nec codes nec 210-70(a)(1)
- The
dining room is considered to be an extension of the kitchen
according to the nec 210 53b(3)c. If there
is a countertop in the dining room it must have the loads evenly distributed
between the two dedicated small appliance circuits nec
210-11(b). All receptacles on the walls must be connected to
the small appliance circuits and they must be spaced every 6" and
on wall greater than 2' in width. Sliding doors do not count as wall
space.
- Refrigerators
can have their own dedicated 15 or 20 amp circuit nec
210--52-3(b)1.
- Floor
receptacles to satisfy the wall space requirement for outlets (not the
countertop outlets) shall be place 18" or closer to the wall in
the floor. nec 210-52(b)3(c)5.
- Maximum
number of outlets
nec 220-3(b)9.
3 watts/sq ft. Maximum load allowed on a 20 amp circuit is 20% of its
rating or 16 amps, and for a 15 amp circuit 20% of its rating or 12
amps. nec 210-21Bb)2.
- Substitution
a three prong outlet on a two prong, 2-wire circuit can be done if you
use a GFCI on that circuit and clearly label all other outlets it feeds
with a GFCI label nec 210-7(d).-3(b)
- The
maximum height you can place a switch on a wall is 6'7". nec380-8
Switch plate must fit flush to the wall nec
380-10(b).
- No
splices allowed concealed in the walls nec 424-40.
- Under
cabinet receptacle outlet strips. Talk to your inspector. If the
strips are UL listed in the White Book they can probably be used
in place of wall mounted receptacles. The problem here is that the
strips can be removed later leaving the walls without adequate outlet
receptacles. Outlets are placed in the bottom of kitchen cabinets
on islands and peninsular countertops but they are firmly built in.
Inspectors have specific times of the day in which they take calls
from the public. Get their name, write it down, and leave yours if
you can.
- This
web site is for use by competent people who have mechanical and electrical
skills. Read and verify the subject matter here using other sources.
National electric code reference numbers are given to you in an attempt
to minimize any errors that may occur in the writing of these web
pages.
Distance
rules
-
Switch and outlet receptacle distance
rules |
| |
Outlet Receptacles |
|
| 6" rule |
An outlet on the face of the kitchen counter lower cabinet cannot
be greater than 6" below the countertop. |
|
| 12" rule |
The outlet on the face of the lower cabinet can be 12"
if there is not an upper cabinet within 18" of the countertop
in which to place an outlet in the bottom of the cabinet . The
code allows 12" if the owner is handicapped. |
|
| 12" rule |
Countertops wider than 12" must have a receptacle.
As a rule of thumb 9" provides a more user friendly kitchen
for a coffee pot. |
|
| 18" rule |
A receptacle can be placed in the bottom of an upper cabinet
within 18" of the countertop. 1999 nec code. |
|
| 20" rule |
A receptacle can be placed in the bottom of an n upper cabinet
within 20" of the countertop. 2002 nec code. |
|
| 24" rule |
Wires cannot be run together through joists and
studs more than 24" |
|
| 2' rule` |
A small appliance with a 2" cord must reach an outlet when placed anywhere on the kitchen countertop. Even though you have two foot reach the linear distance between outlets when two walls meet should be 4 feet or less. |
|
| |
|
|
| |
|
|
% |
Percentage
rule for wiring loads |
NEC code |
| 50% |
Built-in appliance maximum |
|
| 80% |
Continuous load of circuits |
|
| 100% |
3000- watts for countertop loads when calculationg house electrical
loads. |
|
| 110% |
|
|
| 125% |
Circuits for electric heaters must be at 125% of load. |
|
| 3%, 5% |
Advisory rule 2% voltage drop in main service and feeder and 3%
voltage drop in individual circuits.. |
|
More
info: See link placing
outlets, and placing switches
Wiring Hazards
in Kitchens
- When wiring the disposal and dishwasher with a 12-3 wire make sure
the white (neutral) wire is firmly fastened to the neutral bar at the
subpanel. If the white wire comes loose the dishwasher
motor will burn out when the disposal is turned on at the same
time the dishwasher is turned on. If you have spliced the 12-3 wire
anywhere along its length be sure the wires are joined in a professional
manner.
Return to Home page
- Carefully make-up the ground connection inside the garbage disposal.
When plastic water hoses and drain pipes are installed years later,
an internally shorted disposal will electrify the metal parts of the
sink. Thus, touching the drain flange and the water faucet at the same
time will induce a shock.
- When working around copper water pipes, remember a "hot wire" touching
the pipe can easily puncture the pipe. Also: Remember
to locate any new outlet receptacles near the bottom and to the side
of the drain pipes. If you place the outlet in the line of sight someone
could electrocute themselves reaching their arm over the pipe and touching
a hot wire.
- Consider using adjustable plastic boxes for countertop receptacles.
An electrical inspector can have you reset the boxes if they are not
within a quarter of an inch of the surface of the wall. If you have
set tile or granite as the backsplash this could be costly. Recheck
wiring in walls very carefully where tile and granite are to be used.
- When setting outlet boxes along a countertop do not measure the
height for the box off the floor. Use a level to set a level line or
if this is not possible measure the heights off the ceiling. Many floors
are un level. When cabinet makers install cabinets they set the counter
level, not off the pitch of the floor.It helps to set the line of outlets
level in case you ever want to install tile. The line of grout will
reveal any differences in the height of the receptacles.
- Install nail plates over wires that pass through stud in kitchens
where cabinets are to be installed. Cabinet installers use 3" screws
that can easily pierce wires running through studs. If possible run
your wires in the space between the bottom of the dish cabinets and
the countertop.
- Wood drilling bits can drill through galvanized water pipe particularly
if the tip of the bit is hardened to cut through nails in studs. When
drilling through a wall top plate in to space such as an attic do not
push the drill more than an inch about the top of the plate. These
drill bits can chew up wire and pipes faster than a person can control
a drill.
- Nail plates placed over wires to protect them
from nail gun nails do not stop the nails. When an earthquake
shear wall is being installed make sure all the wires are drilled
in straight lines so that the installer can mark the plywood in advance
where the wires are located. Nails used for shear walls will penetrate
wires drilled in the center of a stud.
- When new plywood is installed on the outside walls some architects
call for 2 1/2" nails three to four inches apart. At he joint
of two sheets of plywood there is Molly about an inch and a half to
drill through the stud and not hit a nail. When you do hit a nail it
sometimes times backs out of the wood a half an inch. Later a carpenter
will come along and hammer it back in if you do not totally remove
the nail and mark the spot with red chalk.
- Metal staples can crush romex wire and short the wires. It is in
the interest of the careful electrician to check the operation of all
wiring in a kitchen prior to closing the walls. A crushed wire will
cause a circuit breaker to trip of a GFCI outlet receptacle to trip.
- When adding a GFIC to existing two wire power be aware that metal
romex clamps and metal box clamps will in certain circumstances short
the hot lead to the ground wire causing the ground in the GFCI to become
electrified. Do not tighten metal clamps too tightly.
- Leave 4-6" slack in wiring so that you can later adjust up
or down an outlet box. Nevertheless, staple the romex slightly loose
within 8" of an outlet box. You can leave a loop above the top
plate or under the bottom plate. Run the wire in a square pattern instead
of tightly delivering them to each outlet book. Leave a foot of slack
near recessed lights, house owners are always changing their minds
about the placement of recessed lights.(More
info)
- When working in kitchens around installed gas stoves, be aware that
bumping some flexible gas lines will result in gas leakage. Ridged
metal gas pipes can and do break where the threads end on the pipe.
The metal crystallizes over time and the pipe just snaps off . This
is particularly dangerous in basements where there is a gas water heater
and you crawl over a pipe nearby, and break it. Although this is very
rare it does occur.
- Installing recessed lights in ceilings that have insulation requires
insulated lighting fixtures. California codes do not allow recessed
lights to be boxed in with plywood. You cannot put the non-insulated
housings up against the wood or ceiling of a joist bay. 2" clearance
is required
- There are some kitchens in very old houses that still have gas pipes
installed inside the light junction box for gas lighting. Before cutting
the pipes off, be aware that some of these gas lines are still connected
to the gas service.
- Do not install metal outlet or switch plates on receptacles that
do not have a ground wired to the switch or duplex outlet. NEC
380-9
- When
using 12-3 or 14-3 wire to deliver two circuit in one wire be sure
to install a common-trip two-pole circuit breaker in the main or
sub panel. 240 volts is present on the end of a multi
conductor cable. Turning one leg of the 240 v off leaves the other
leg energized. When a person is working on a disposal/dishwasher
outlet under the sink they are in a confined area that could be
hazardous to their health if one leg of the dishwasher/disposal
circuit is still energized.
- Using 12-3 wiring can lead to appliance burn-outs. The neutral to
wire must be firmly connected between the breaker box and the receptacles. A
dishwasher on a 12-3 circuit will burnout when the disposal on the
same wire is turned on when the white (neutral) wire is disconnected
or poorly connected.
- Drilling floor or ceiling joists in the wrong place destroys their
structural strength. If you have 12" ceiling joists then the holes
you drill must run horizontally along the beam 6" from the top
or bottom of the joist. Space the holes several inches apart horizontally.
Do not drill holes larger than an inch without approval of a general
contractor, architect, or engineer.
| You cannot drill into prefabricated Glu-Lam
or Paralam beams or joists without following the drilling instructions
that come with them. An engineer or architect can specify the
drilling patterns in joists. |
- If you are drilling a large number of holes horizontally in joists
contact your local inspector for the location of the holes. Many inspectors
prefer small holes be drilled horizontally in the outer two-thirds
of the joist, each hole being separated horizontally by a few inches
of distance. Three-quarters of an inch is a small hole. Drawing
- You cannot cut a notch on the edge of a joist.
If you start with a 2 X 12" joist and you cut a 2" notch
in it, it is no longer considered by engineers to be a 2 X 12. It is
now considered to be a 2 X 10 joist. Never, ever,
notch floor and ceiling joists.
- You cannot place an un insulated recessed light housings near wood.
The instruction call out the distance, usually 2" from flammable
material. You cannot fill around an insulated housing with insulation,
nor can you in California build a box around the fixture to keep the
insulation away.
- You cannot bury junction boxes with wires in
them under plaster. Not only is this an electrical hazard
it is annoying for electricians trying to trace an electrical problem
in a house. Since they cannot find these boxes they usually will
rewire the circuit at great expense to the owner. Many a home-owner
has had to pay anywhere from five-hundred to fifteen-hundred dollars
to have a new circuit installed because the old circuit connections
came loose in the buried junction box.
- Note: leaving romex wire hanging from the ceiling
at eye level can damage one's eye. It is best to bend a little
loop at the end of the romex to keep the sharp edge of the wire from
poking your eye when you get in a hurry or walk through the kitchen
in the dark.
- Warning When removing tile from the
walls of old kitchens be aware when hammering or prying on tile, that
chard's of broken tile fly farther than you might expect, and they
are extremely sharp. Wear safety glasses.
- Ladders are dangerous. You might not think they are. There are 500,000
accidents a year involving ladders, costing 11 billion dollars in medical
costs. It is difficult enough to avoid accidents on good ladders without
having to deal with a rickety one. If you are working with an 8' ladder
and a hammer is laying on top it will of course fall. Sometimes open
sheetrock knives are left on ladders. Be aware of looses shoes on extension
ladders. As you climb down the ladder you easily can slip at the place
where two parallel rungs side by side suddenly change to one rung.
Angle drills will fall when you fall, and sometimes the drill bit will
impale the person when they fall on top of it.
- When working under the sink be aware that if you get a shock because
you left the power on you can hurt yourself because you are trapped
in a confined space. At a minimum your arms will hit the cabinet in
a most painful way. If the power to the receptacle under the sink is
a 12-3 wire the circuit breaker must have a "common trip" handle
to shut off both circuits at once.
- When drilling in tile remember that chard's of tile are sharper than
metal or wood shavings and can hit a person in the eye well beyond
arms length. It takes years of near misses for electricians to realize
how dangerous drilling or chiseling tile is. When working with tile
wear gloves and wear protective glasses.
| Danger: If
you are adding outlets in a kitchen using knob and tub
wiring as a source of power be aware that while a GFCI
makes a legal receptacle for two wire to three-wire conversions
it does not prevent the very dangerous back feeding of
power into the ground wire in the new romex wire you are
using when a metal clamp short the hot to the ground when
over tightening the clamp. Add a solid ground wire to the
kitchen water pipes, both the hot and cold pipes together
at the water heater and make sure there is a grounding
wire from the main panel at the meter running to within
5" of where the water line enters the house. |
- Placing outlet boxes in Firewall's:
Do not forget these requirements.
- Volume 1 of the
2003 edition of The UL Fire Resistance Directory contains the information
necessary to properly place outlet boxes in fire rated walls. Please
note in fire rated wall 1. the outlet boxes must be rated for firewall's,
2. outlet boxes placed on the other side of a firewall must be at
least 24" away (horizontally in any direction). Do not place
boxes back to back in the same stud bay.
- Sheetrock Hazards Whether
you are having sheetrock installed or installing itself be sure to
map out where outlets and switches are. It is not uncommon for installers
to cover an outlet or recessed light. Sometimes installers stuff paper
in low voltage recessed lights to push the wires up into the can, but
sometimes they push up the wires and the bulb which
can ignite the paper.
- Design Hazards
- Before installing outlet boxes determine the height of the baseboards.
In old home the baseboard is 10" so if your outlets are 12" on
center you will have a design problem
- Before installing countertop outlet boxes determine the height of
the countertop including the back splash. Leave at least 2" of
height above the backsplash for proper conventional placement of outlets.
- Determine the width of the molding around the door and windows before
installing switch and outlet boxes. Conventional designs place the
edge of the outlet box 2-4" from the molding.
- Do not forget other types of wire for the kitchen such as telephone,
network, cable TV, security and doorbell wiring.
Return
to Home page
wiring kitchen
materials
list
This web site is for use
by competent people who have mechanical and electrical skills. Read
and verify the subject matter here using other sources.
Copyright ©2005 dp
All rights reserved
This
web site is for use by competent people who have mechanical and
electrical skills. Read and verify the subject matter here using
other sources. National electric code reference numbers are given
to you in an attempt to minimize any errors that may occur in the
writing of these web pages.
The author of these web
pages takes absolutely no responsibility
for errors in the text that might result in costly rewiring.
Every attempt is made to be accurate. This information is free
and frivolous running around blaming writers for every situation
that goes wrong discourages the free flow of information to the
community that badly needs perspective on issues such as electrical
wiring. All electricians rely on the Nation Electric Code. Rely
on the NEC code as the final word on what is to code and what
is not.
Copyright © 2005
DP
All rights reserved
Copyright
© 2003-2005 DP
All rights reserved
|
|
|
|
|
|
|